Redundant safety, millisecond response, and global certifications — integrate the last line of defense into your cabinet with LINKWELL EPO.
- ≤ 20ms trip
- -40°C to +85°C
- IP69K / IK10
Engineered for fail‑safe disconnection
Designed to meet IEC 60947‑5‑1, EN ISO 13850, and UL 508 – direct opening action with forcibly guided contacts.
Positive opening
- NC contacts forced open by non‑resilient mechanism
- No spring‑return – ensures break even if welded
- Silver alloy contacts, self‑cleaning
Contact variants
- 1NC / 1NO + 1NC / 2NC
- gold‑plated for dry circuits
- 600V AC / 220V DC ratings
Environmental sealing
- IP66, IP67, IP69K (high‑pressure washdown)
- front panel sealing, corrosion‑resistant metal
- IK10 impact resistance (20 J)
Actuator styles
- Mushroom Ø30 / Ø40 · flush · key‑release
- Twist‑to‑release / pull‑to‑release
- Illuminated (LED 24V) versions
Emergency Power Off Buttons Type
Emergency Power Off Buttons for outdoor applications feature waterproof and weatherproof designs. Built with sealed housings and corrosion-resistant materials, they ensure reliable performance in industrial, marine, and harsh environmental conditions, providing immediate safety shutdown when needed.
Mushroom Head Push Buttons
Large, easy-to-hit surface
Twist-to-reset or pull-to-reset mechanism
Best for high-traffic industrial areas
Flush or Low-Profile EPO Buttons
Requires authorized personnel to reset
Adds extra safety layer in sensitive applications
waterproof push button switch 12v
Less likely to be triggered accidentally
Suitable for control panels with space constraints
Application of Emergency Power Off Buttons in Different Industries
Data Centers
Manufacturing & Industrial Plants
Healthcare Facilities
Technical specifications – LK‑EPO series
Designed to meet IEC 60947‑5‑1, EN ISO 13850, and UL 508 – direct opening action with forcibly guided contacts.
| Parameter | 22mm Compact | 30mm Heavy Duty |
|---|---|---|
| Rated insulation voltage (Ui) | 600V AC | 1000V AC |
| Thermal current (Ith) | 10 A | 16 A |
| Utilization category | AC‑15 / DC‑13 | AC‑15 / DC‑13 |
| Contact blocks | 1NC / 1NO + 1NC / 2NC | 2NC / 3NC + optional NO |
| Positive opening force | > 50 N | > 80 N |
| Mechanical endurance | 1,000,000 cycles | 500,000 cycles (heavy duty) |
| Protection class | IP66 / IP67 / IP69K | IP66 / IP67 / IP69K |
| Ambient temperature | -40°C … +70°C | -40°C … +85°C |
| Terminal type | Screw / Spring‑cage | Screw / Ring tongue |